District Cooling Services Supply Code
Clause 3Status unknownSaudi ArabiaRegulation
Issued by Saudi Electricity Regulatory Authority (sera.gov.sa)
DISTRICT COOLING SERVICE OBLIGATIONS
3-1 Supply Temperature
3-1-1 The Licensee shall operate the System and Service Connection Facilities to regulate the
Supply Temperature within 6°C ± 0.5°C under Normal Operating Conditions.
3-1-2 The Consumer shall ensure that the Return Temperature shall be 14°C or higher or such
other Temperature that may be agreed between the Parties.
3-2 Supply Availability and Reliability
3-2-1 Subject to Section 3.2.3, the Supply shall be provided at all times on a 24 hourly basis.
3-2-2 The Licensee shall operate and maintain the System such that the Availability of Supply
with respect to any calendar year shall be at least 99.5%.
3-2-3 The Licensee may schedule interruptions to the provision of District Cooling Service at
the Premises for the purpose of maintenance, repair, connection, disconnection,
extension and other work in the System (“Planned Interruption”) provided that:
(a) Except for operational emergency arising from any fault in the System, the Licensee shall
give the Consumer at least 14 days' prior written notice stating the date(s) on which the
Planned Interruption will occur; the duration of the Planned Interruption;
(b) the Licensee shall to the extent possible, carry out the Planned Interruption outside the
Normal Usage Hours.
Public
District Cooling Services Supply Code
The Arabic text is the legally binding version. The English translation is provided for guidance only.