Saudi Arabian Grid Code May 2024
Para. 7.1.1Status unknownSaudi ArabiaRegulation
Issued by Saudi Electricity Regulatory Authority (sera.gov.sa)
In order to properly account for the flow of electricity through the
Transmission System, it is imperative that suitable and accurate metering and
recording facilities are provided at all Connection Points on the Grid. This
chapter, therefore, deals with metering and recording requirements for
Participants and clarifies on their obligations relating to such installations. It
also sets the minimum technical, design and operational criteria to be
complied with by Users relating to metering and data collection Equipment
and installations.
7.1.2 The provisions of this chapter are specifically applicable to issues relating to
the following:
(i)
supply, installation, and maintenance of Metering Equipment (Main as
well as Check) and their testing and calibration;
(ii)
collection, storage, and communication of metering data; and
(iii)
competencies and standards of performance of Participants relating to
metering.
Objective
The objective is to set out the responsibilities of the Participants relating to
measuring and recording of Active and Reactive Power flows and Energy
imports into or exports out of the Grid and also to specify the terms and
conditions that will govern the metering and recording Equipment and
systems employed for the above purpose.
Metering Responsibility
7.3.1 The TSP shall be responsible for managing and collecting metering
information and shall ensure that all points identified as Metering Points in the
relevant Connection Agreement have proper metering facilities.
7.3.2 The User shall be responsible to provide Meters and the associated
Equipment and facilities at the Connection Point and offer these for installing
and sealing by the TSP along with proofs of certification in respect of Meters
and the CTs and VTs by an accredited laboratory as set out in (7.3.4) below.
Chapter 7 - Metering Code
The Saudi Arabian Grid Code
Updated Version: May 2024
7.3.3 The User shall also be responsible to demonstrate that its Metering
Equipment meets all the technical requirements and standards set forth in this
chapter.
7.3.4 Prior to making them available to the TSP for installing and sealing, the Users
shall submit the Meters for certification to an independent laboratory
accredited for such purposes by the Saudi Accreditation Center.
7.3.5 The TSP shall ensure that installation, Commissioning, maintenance,
auditing, and testing of Metering Equipment and allied systems are done in
accordance with the standards as specified in the relevant Connection
Agreement.
7.3.6 Notwithstanding (7.3.2 to 7.3.4) above, once installed, all Main Meters shall
be owned and operated by the TSP.
7.3.7 The User shall also provide to the TSP all the information that the TSP will
reasonably require to perform its metering duties properly.
Metering Equipment
The Metering Equipment at the Connection Point shall consist of:
(i)
Meters;
(ii)
Instrument Transformers;
(iii)
Lightning Protection; and
(iv)
All other interconnecting electric/telecommunication cables, wires, and
associated devices, etc.
Metering Point
7.5.1 The Metering Point shall be at the Connection Point on the Transmission
System, as specified in the relevant Connection Agreement.
7.5.2 The Actual Metering Point may differ from the Connection Point, if agreed by
the TSP and the User. The accuracy requirements of the Metering Code then
shall apply to the Actual Metering Point.
7.5.3 Where the Actual Metering Point and the Connection Point do not coincide,
then, where necessary, compensation for Power transformer and/or line
losses shall be provided. The compensation may be applied locally within the
Metering Equipment or remotely. In both cases, however, compensation
factors and the justification for them must be recorded.
Chapter 7 - Metering Code
The Saudi Arabian Grid Code
Updated Version: May 2024
Metering Parameters
The Arabic text is the legally binding version. The English translation is provided for guidance only.
Freshness not yet recorded