Saudi Arabian Grid Code May 2024
Para. 7.7.9Status unknownSaudi ArabiaRegulation
Issued by Saudi Electricity Regulatory Authority (sera.gov.sa)
The TSP shall connect a telecommunications medium to the meter/recorder
that will allow for remote downloading of metering data.
Chapter 7 - Metering Code
The Saudi Arabian Grid Code
Updated Version: May 2024
7.7.10 The TSP shall be enabled to remotely interrogate a Meter or recorder on a
daily basis or as mutually agreed with a User.
7.7.11 Meters shall be visible and accessible, but the access to such meters shall be
authorized only by the TSP.
7.7.12 The metering data retrieval by remote link, or by on-Site method in the case
of a persistent telecommunication problem, shall be a secure process
whereby Meters or recorders are directly interrogated to retrieve billing
information from their memories.
7.7.13 The TSP shall be responsible for the validation and substitution of metering
data.
7.7.14 In principle, Check metering data, where available, shall be used to validate
metering data provided that Check Metering Equipment accuracy conforms to
the standards of this section.
Metering Equipment Standards
7.8.1 All Metering Equipment shall comply with the provisions set out in this
Metering Code. These provisions may be revised from time to time in
consultation with the Regulator to take account of changing technologies or
the requirements of the industry.
7.8.2 The Metering Equipment shall be accurate within the prescribed limits for
such Metering Equipment referred to in the relevant Connection Agreement or
set out in the Metering Code.
7.8.3 The accuracy of the various items of Metering Equipment shall conform to the
relevant IEC standards (or their equivalent Saudi national standards).
7.8.4 The Meters shall be calibrated by an independent calibrating agency
accredited by the Saudi Accreditation Center for this purpose. The User shall
provide calibration certificate with expiry date of calibration.
7.8.5 Voltage Transformers (VTs)
(i)
The Voltage Transformers shall comprise three (3) units for a three-
phase set, each of which complies with IEC Standard 60044-2:
Instrument Transformers — Part 2: Inductive Voltage Transformers (or
its equivalent ANSI/IEEE/Saudi national/TSP standard) for metering,
and shall be of the 0.2 accuracy class. These Voltage Transformers
shall be connected in the configuration as agreed in the relevant
Connection Agreement.
Chapter 7 - Metering Code
The Saudi Arabian Grid Code
Updated Version: May 2024
(ii)
The voltage drop in each phase of the Voltage Transformer
connections of the same accuracy and class shall not exceed 0.2 V. It
shall be connected only to a Main Meter with a burden that shall not
affect the accuracy of measurement.
7.8.6 Current Transformers (CTs)
(i)
The Current Transformers shall comprise three (3) units for a three-
phase set, each of which complies with the IEC Standard 60044-1:
Instrument Transformers — Part 1: Current Transformers (or its
equivalent ANSI/IEEE/Saudi national/TSP standard) for metering, and
shall be of 0.2 accuracy class. It is preferred that two (2) Current
Transformer cores with corresponding number of secondary coils per
phase be provided between the connection box and the terminal of the
metering element on the Meter so that the Current Transformer
connections for checking Meter pulses can be completely separated
from those provided for the Meters.
(ii)
The Current Transformer’s rated secondary current shall be either 1 or
5 amperes. The neutral conductor shall be effectively Grounded at a
single point and shall be connected only to a Main Meter with a
burden that shall not affect the accuracy of measurement.