Saudi Arabian Grid Code May 2024
Para. 4.10.7Status unknownSaudi ArabiaRegulation
Issued by Saudi Electricity Regulatory Authority (sera.gov.sa)
Approval of Local Safety Instructions
4.10.7.1 For each Connection Site, the User shall supply to the TSP a copy of its
Safety Rules relating to its side of the Connection Point.
4.10.7.2 The TSP will supply to each User a copy of its own Safety Rules relating to
the TSP side of the Connection Point at each Connection Site.
4.10.7.3 Prior to Connection, each party must agree to the other’s Safety Rules in
relation to Isolation and Grounding.
4.10.7.4 If the User’s Safety Rules are more stringent relating to Isolation and/or
Grounding than those of the TSP, then the User Safety Rules shall apply.
Otherwise, the TSP Safety Rules shall apply.
4.10.7.5 If, after agreement, a party wishes to incorporate a change in its Safety
Rules relating to Isolation and/or Grounding, it shall inform the other party. If
the change is to make the provisions more stringent, then the other party
merely will note the changes. If the change is to make the provisions less
stringent, then the other party will need to approve the new provisions and
the procedures referred to above shall apply.
4.10.8 Safety Representatives
4.10.8.1 Each User shall nominate staff to be designated as User Safety
Representative(s) to be available to Isolate and Ground, to a time scale
agreed in the applicable Connection Agreement, to meet the needs for
repairs that would affect other Users. User Safety Representative will be
responsible for coordinating on Safety with the TSP pursuant to the
provisions of this section.
Chapter 4 - Operating Code
The Saudi Arabian Grid Code
Updated Version: May 2024
4.10.8.2 Each User shall, prior to being connected to the Transmission System, shall
designate to the TSP its Safety Representative(s) and will update the TSP in
writing whenever there is a change to the identity of its Safety
Representative(s).
4.10.8.3 The TSP will, at the time of a User being connected to the Transmission
System, inform in writing to that User of the TSP’s own Safety
Representative(s) (which in most cases will be the TSP Control Engineer)
responsible for coordinating with the User Safety Representative(s) on
Safety issues.