Saudi Arabian Grid Code May 2024
Para. 1.0Status unknownSaudi ArabiaRegulation
Issued by Saudi Electricity Regulatory Authority (sera.gov.sa)
MVA should exercise all precautionary measures to
maintain 85% lagging power factor. For such customers, the minimum
allowable Power Factor will be 90% lagging after five years (from the date of
21-10-1433), and 95% lagging power factor after ten years from the said date.
In case of any deviation from this criteria, a tariff on the reactive power
consumed, exceeding the allowable limit, will be applied as per terms and
conditions given in SERA Board Resolution # 2/27/23 dated 21-10-1433.
Chapter 2 - Connection Code
The Saudi Arabian Grid Code
Updated Version: May 2024
2.5.6.5 Reactive Power compensation shall be provided by the Distribution Entities at
Low Voltage System close to the load point to avoid excessive Reactive
Power losses and to enable the TSP to maintain the Transmission System
voltage within the limits as specified in (2.4.3).
System Services
The relevant Connection Agreement or Power Supply or Purchase
Agreement (as the case may be) will contain requirements for the capability
for certain System Services from the following list which may be needed for
proper System operation:
(i)
Voltage Control and Reactive Power Support (when used exclusively
for such purpose);
(ii)
Demand Side Response;
(iii)
Primary Control of Generating Units;
(iv)
Secondary Control of Generating Units;
(v)
Black Start Capability;
(vi)
Operating Margin (Operating/Contingency Reserve);
(vii)
Fast Frequency Response;
(viii)
Reduction or increase in Active Power due to a System Constraint;
(ix)
Interruptible Load; and
(x)
any other System Service.
Site Related Conditions
2.7.1 Responsibility for Operation and Maintenance
In the absence of an agreement between the parties to the contrary,
operation and maintenance responsibilities shall follow ownership.
2.7.2 Responsibilities for Safety
2.7.2.1 Any User entering and working on its Plant and/or Apparatus on a TSP Site
shall work to the TSP Safety Rules.
2.7.2.2 The TSP entering and working on its Plant and/or Apparatus on a User Site
shall work to the TSP Safety Rules. However, for User Sites where the TSP
staff may be exposed to some special risks (for instance, hazardous or toxic
substances or gases, etc.), the TSP, in addition to its own Safety Rules, will
follow the User Safety Rules also.
Chapter 2 - Connection Code
The Saudi Arabian Grid Code
Updated Version: May 2024