Voltage Withstand Capability Diagram
2.5.5.24 The Renewable Resource Generating Unit shall remain connected to the
Network and continue stable operation if none of the phases exceeds 120%
of nominal voltage for more than 1s.
2.5.5.25 Each Power Park Module which does not inherently provide short-circuit
power and which has a Registered Capacity greater than twenty five (25)
MW in aggregate, may be required by the TSP to provide dynamic voltage
support during network disturbances. This dynamic voltage support is
described by the following:
i.
The magnitude of the additional reactive current injection shall be
determined as a linear function of the positive or negative voltage
change (ΔU) with respect to the pre-disturbance value with total
reactive current injection limited to 100% of rated current.
ii. The dynamic voltage support shall not have priority over AVR and
active power control of the generating units in the normal voltage
range and in the 30-minutes range defined in (2.4.3).
iii. The droop of this linear function shall be adjustable on request of the
TSP from 0 additional reactive current injection (minimum droop) to
an additional reactive current injection of 2% of the rated current per
percent of the voltage drop (maximum droop).
iv. If necessary, the active current shall be limited to enable dynamic
voltage support.
Time
Voltage
(p.u.)
1.3s
0.3s
30min
SGU
PPM
Chapter 2 - Connection Code
The Saudi Arabian Grid Code
Updated Version: May 2024
v. In case of overvoltage, the additional reactive current shall have an
inductive behavior and in case of undervoltage, the additional reactive
current shall have a capacitive behavior.
vi. The additional reactive current shall bring the total reactive current
injection to at least 2/3 of the target value within 20ms (control
response time) and this target value shall be reached with an
accuracy of 10% within 60ms from the moment the voltage deviation
occurs.
vii. The dynamic voltage support shall be maintained for at least 400 ms
after voltage recovery in the normal voltage range, or in the 30-
minutes range defined in (2.4.3).
viii. The transitions between dynamic voltage support and voltage control
defined in 2.5.5.17 shall be smooth.
ix. In case of unsymmetrical faults, the dynamic voltage support shall not
escalate the overvoltages of the healthy phases above the maximum
voltage defined in (2.4.3).
2.5.5.26 All Power Park Modules that remain synchronized to the network following a
disturbance shall be able to recover Active Power output after fault
clearance or after voltage regains levels specified in (2.4.3).
The recovered Active Power output shall be higher than 90 % of the pre-fault
value within 4 seconds after fault clearing unless prevented by the reduction
of available active power.
2.5.5.27 Generating Units shall be capable of withstanding, without tripping, a
negative phase sequence loading appropriate to their rated full load in
accordance with the IEEE Standard C37.102-1995: IEEE Guide for AC
Generator Protection. In addition they shall be required to withstand, without
tripping, the negative phase sequence loading incurred by clearance of a
close-up phase-to-phase Fault by backup Protection on the User System of
which they are a part.
2.5.5.28 The higher voltage windings of the Generating Unit step-up transformer
connecting the Generating Unit to the Transmission System must be star
connected with the star point grounded in accordance with IEEE Standard
C37.101-1993: IEEE Guide for Generator Ground Protection. If adjacent to a
TSP Substation, it shall be connected to the Grounding System of that
Substation.
Chapter 2 - Connection Code
The Saudi Arabian Grid Code
Updated Version: May 2024
2.5.5.29 Generators will be responsible for protecting their Generating Units against
the risk of any damage which might result from any frequency excursion
outside the range 57.0 Hz to
The Arabic text is the legally binding version. The English translation is provided for guidance only.