BESS response during normal, high, and low frequency
2.5.5.18 Each Renewable Resource Generation shall be capable of regulating its
Active Power in the frequency range [57Hz, 59.8Hz] through modulation of
the Active Power as a function of frequency deviations below 59.8Hz. The
Active Power Droop shall be adjustable within 2% and 8%. The normal set
point shall be generally at 4%. Output power shall be limited by the available
output power and the minimum output power of the Generating Unit.
2.5.5.19 The Active Power output of the Renewable Resource Generation connected
to the Network shall be controllable as long as technically feasible based on
the Available Active Power.
i.
The Renewable Resource Generation shall be capable of receiving a
Dispatch Instruction containing a required setpoint of Active Power
output, of absolute Active Power Limitation, of Active Power delta
Regulation and of Active Power Gradient, manually or through
automatic remote control system.
ii. Generation shall be able to manually or automatically take into
account the Dispatch Instruction.
iii. As long as the Active Power Output is not limited by the Available
Active Power, the accuracy of the control performed and of the
setpoint shall not deviate by more than 2% of the setpoint value or by
0.5% of the rated power, depending on which yields the highest
Chapter 2 - Connection Code
The Saudi Arabian Grid Code
Updated Version: May 2024
tolerance and shall be reached in less than 10 minutes after the
reception of the Dispatch Instruction.
2.5.5.20 Each Synchronous Generating Unit shall be equipped with high response
Excitation System with continuously acting Automatic Voltage Regulation
(AVR) system to control the Unit terminal voltage. The AVR shall be designed
and operated to maintain the steady-state terminal voltage within ± 0.5% of
the set point in the normal voltage range as specified in (2.4.3) without
instability over the entire operating range of the Unit. Ceiling voltage for static
Exciters shall be at least twice, and for brushless Exciters at least 1.6 times
the rated field voltage of the Generating Unit. The Excitation System shall be
capable of supplying its ceiling voltage for 10 seconds. Generators shall not
disable this automatic control mode without prior approval of the TSP.
Each Synchronous Generating Unit shall be required to include Power
System Stabilizing (PSS) and var limiting Equipment as well. The PSS shall
be tuned to provide positive damping to local as well as inter-area mode of
oscillations in the frequency range of 0.15 – 2.0 Hz. For generating units that
were added to the network before January 1, 2022, and furnished with single
input PSS, shall be tuned to optimum capability, unless required by the TSP
to comply with 0.15 – 2.0 Hz range based on justified technical requirements
for the Generators.
The PSS shall remain in service all the time except when synchronizing or
when generation unit is at low load and based on control logic for protecting
the unit or justified by the manufacturer and agreed by TSP.
Each Power Park Module shall, at minimum, be able to provide reactive
power automatically by the following control modes during normal operation:
Voltage control mode;
Reactive power control mode;
The selected control mode shall maintain the steady-state terminal voltage
within ± 0.5% of the normal voltage range specified in (2.4.3).
The damping ratio of the output reactive power of each Power Park Module
shall be at least 0.05.
Each Power Park Modules which has a Registered Capacity greater than
twenty five (25) MW in aggregate, shall be equipped with a Power Oscillation
Chapter 2 - Connection Code
The Saudi Arabian Grid Code
Updated Version: May 2024
Damper (POD) capable of increasing or decreasing the output power in such
a way to minimize the power oscillations in the low frequency range (0.15 –