Saudi Arabian Grid Code May 2024
Para. 57.0Status unknownSaudi ArabiaRegulation
Issued by Saudi Electricity Regulatory Authority (sera.gov.sa)
Hz, all Generating Units shall remain in synchronism with the Transmission
System for the operating times stated in (2.4.2) to allow the TSP to
undertake measures to correct the situation. Each Generating Unit must be
capable of contributing to, in a manner satisfactory to the TSP, Frequency
and Voltage Control by modulation of Active Power and Reactive Power
supplied to the Transmission System or a User System.
Chapter 2 - Connection Code
The Saudi Arabian Grid Code
Updated Version: May 2024
2.5.5.13 The System frequency could vary within the limits given in (2.4.2) and
Generating Units are required to be capable of satisfactory operation at any
frequency within this range unless the TSP has agreed in the Connection
Agreement to the use of any frequency-level relays and/or rate-of-change-
of-frequency relays which will trip Generating Unit within this frequency
range.
2.5.5.14 Each Synchronous Generating Unit shall be fitted with a fast-acting Speed
Governor System to provide Power and Frequency Control under normal
operating conditions.
The Speed Governor System shall be designed and operated freely to
regulate System frequency and shall have adjustable Governor Droop
setting within 2% to 8%. The normal set point shall be generally at 5%.
Total Governor Deadband (inherent plus intentional) shall be 0.05 Hz or
less.
The above Droop and Deadband requirement shall apply for an entire
combined-cycle Generation facility. Users shall not change frequency or
load related control settings of Speed Governors without the prior
agreement of the TSP.
In islanding situations, the Generating Unit’s Speed Governor System shall
also be able to operate at frequency range between 57.5 Hz and 60.2Hz.
Each Power Park Module shall be capable of regulating its Active Power
under normal operating conditions through modulation of the Active Power
as a function of frequency deviations. The Active Power Droop shall be
adjustable within 2% and 8%.
The normal set point shall be generally at 5%. Total Frequency Regulation
Deadband (inherent plus intentional) shall be 0.05 Hz or less.
Frequency Regulation from Renewable Resource Generation shall be
activated or deactivated automatically following a request from the TSP.
Each Renewable Resource Generation shall be capable of regulating its
Active Power in the frequency range [60.2Hz, 62.5Hz] through modulation
of the Active Power as a function of frequency deviations above 60.2Hz.
The Active Power Droop shall be adjustable within 2% and 8%. The normal
set point shall be generally at 4%. Output power shall be limited by the
Chapter 2 - Connection Code
The Saudi Arabian Grid Code
Updated Version: May 2024
available output power and the minimum output power of the Generating
Unit.
The overall requirements for the normal operating range of Active Power in
the event of frequency and voltage deviations for a BESS facility at the
point of Connection as shown in Figure 2.3 below. The frequency
deviations below 57.5 Hz and above 61.5 Hz shall be according to Clause
Figure
The Arabic text is the legally binding version. The English translation is provided for guidance only.