Saudi Arabian Grid Code May 2024
Para. 2.2Status unknownSaudi ArabiaRegulation
Issued by Saudi Electricity Regulatory Authority (sera.gov.sa)
Maximum Output Power Reduction Diagram
2.5.5.3 The accuracy of frequency measurement for Frequency Regulation shall be
+/- 10mHz or better.
2.5.5.4 All Synchronous Generating Units shall be capable of withstanding any Rate
of Change of Frequency (RoCoF) up to 1Hz/s without disconnection from the
network other than triggered by loss of mains protection. The Rate of Change
of Frequency shall be measured over a sliding 500ms time period.
All Power Park Modules shall be capable of withstanding any Rate of Change
of Frequency up to 2.5Hz/s without disconnection from the network other than
triggered by loss of mains protection. The Rate of Change of Frequency shall
be measured over a sliding 500ms time period.
2.5.5.5 Each Power Park Module, which is not inherently capable of supplying
additional Active Power to the network by its inertia and which has a
Registered Capacity greater than twenty five (25) MW in aggregate, shall be
capable of providing Synthetic Inertia through the supply of additional Active
Power output to the network in order to limit the Rate of Change of Frequency
following a sudden system unbalance.
2.5.5.6 For Inverter-Based Resource facilities, the SCR at its Connection Point
should be > 3.0. If the SCR is < 3.0, the User shall conduct a detailed
electromagnetic transient study to evaluate the PPM or BESS connection and
verify its compliance and its stable operation.
Chapter 2 - Connection Code
The Saudi Arabian Grid Code
Updated Version: May 2024
2.5.5.7 The Active Power output at the Generating Unit terminals under steady state
conditions should not be affected by voltage changes in the normal operating
range specified in (2.4.3).
2.5.5.8 Transformation ratio and the tap changer of the step up transformer and the
auxiliary services transformer, the voltage range of the Generating Unit, the
control capabilities and converter ratings of the Power Park Modules and
Excitation of the Synchronous Generating Unit shall be designed and
adjusted so that the Generating Unit is at normal operating voltage of the
Grid, capable of producing or absorbing (as the case may be), continuously
the Reactive Power defined by the capability curve of the Generating Unit (at
Generating Unit voltage level). The Generating Unit’s continuous Reactive
Power capability shall not be restrained by main or auxiliary Equipment,
control, Protection, or operating procedures.
2.5.5.9 The Synchronous Generating Unit shall be capable of continuously absorbing
the Reactive Power (under Excitation operation) defined by the capability
curve of the Generating Unit also at maximum voltages (380, 230, 132, 115,
and 110 kV of the Grid) assuming that Stability is maintained.
2.5.5.10 The Reactive Power output at the Generating Unit terminals under steady
state conditions and at rated Active Power should be fully available within
the range ± five (5)% of nominal voltage at the Connection Point.
2.5.5.11 The TSP may require a Black Start capability from certain strategically
located Generating Units/Stations. In such cases, Generators will provide
Black Start capability through an agreement with the TSP. If an agreement
cannot be reached on this issue, the TSP or the Generator shall refer the
matter to the Regulator for resolution. Generators, committing to provide
Black Start capability, shall also allow to the TSP access to their Black Start
Units for testing and drills, as and when required by the TSP.
2.5.5.12 In case the System frequency momentarily rises to 62.5 Hz or falls to